Round physical dimensions upward and recheck usable capacity; do not round down.
The theory behind it
Method used: Required usable volume ÷ internal plan area + freeboard + unusable bottom depth
Size the sump from demand first, then check a proposed internal rectangle. Only the water between the lowest usable level and the maximum operating level is available. Outside walls, excavation size, freeboard and water below the pump intake are not usable storage.
Assumptions used
•135 L/person/day is a selected residential planning rate, not a guarantee of actual consumption or a universal local approval requirement. BIS Table 48 gives conditional ranges of 100–135 and 150–200 L/person/day; confirm the applicable local requirement.
•Domestic demand covers drinking, cooking, bathing, flushing, laundry, utensils and household cleaning together. Do not add these again on top of the per-person allowance.
•Gardening, car washing and other uses are entered separately only when not already covered. Car-wash water depends on hose/bucket/equipment and is not a fixed standard.
•Reserve days and overhead-tank share are editable supply-reliability assumptions, not mandated NBC storage ratios. Sump reserve and overhead storage are reported separately, not counted twice as days of autonomy.
•Fire reserve, pools, commercial use, construction water and municipal network losses are excluded. Required fire water must be separately designed and protected from domestic drawdown.
•Choose occupancy for full expected use, including regular residents; add visitors' demand under other daily uses. Use meter readings to refine the per-person allowance.
•150 mm freeboard and 100 mm bottom depth are editable example allowances, not universal code minima. Confirm overflow level, pump intake and cleaning details.
•Dimensions are clear inside faces. IS 3370 structural and watertightness design, groundwater uplift, wall/slab thickness and safe access require an engineer; this is not a reinforcement design.
Codes & references
BIS SP 73:2023, Table 48 — residential demand depends on population, full flushing, housing category and water availability. https://www.bis.gov.in/wp-content/uploads/2024/02/SP-732023-Standardized-Development-and-Building-Regulations-2023.pdf
IS 3370 — concrete structures retaining liquids; NBC Part 9 Section 1 — water supply.